11 diagnostics – Lenze E94AYCET User Manual
Page 86

11
Diagnostics
11.1
LED status displays
86
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
ERR
red
off
No fault
blinking
The configuration is invalid/faulty.
blinking once
(single flash)
• A non requested state change has occurred. (The slave application
has autonomously changed the EtherCAT status.)
• Synchronisation error (The EtherCAT node automatically changes to
the "Safe-operational" state.)
blinking twice
(double flash)
An "Application Watchdog Timeout" or a "Sync Manager Watchdog
Timeout" has occurred.