Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

29

5

Installation

5.2

Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.5

External voltage supply

The communication module can be supplied externally with voltage via separate supply cables at

the 2-pole plug connector X245.

External voltage supply of the communication module is necessary if the bus communication is to

be continued in the event of a failure of the supply of the standard device.
Access to parameters of a standard device disconnected from the mains is not possible.

Assignment of the X245 plug connector

Terminal data

Note!

With external voltage supply, always use a separate power supply unit, safely separated

to EN 61800-5-1 in every control cabinet (SELV/PELV).

Designation

Description

+

U = 24 V DC (20.4 V -0 % ... 28.8 V +0 %)

I = 130 mA

-

Reference potential for the external voltage supply

Area

Values

Electrical connection

2-pole plug connector (spring connection/screw connection)

Possible connections

Fixed:

1.5 mm

2

(AWG 16)

Flexible:

Without wire end ferrule

1.5 mm

2

(AWG 16)

With wire end ferrule, without plastic sleeve

1.5 mm

2

(AWG 16)

With wire end ferrule, with plastic sleeve

0.5 mm

2

(AWG20)

Starting torque

0.5 ... 0.6 Nm / 4.4 ... 5.3 lb-in (only with screw connection)

Stripping length

6 mm with screw connection
9 mm with spring connection