Commissioning

6.5

Establishing an online connection with the »Engineer«

44

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to use the EtherCAT ADS communication path:

1. Highlight the desired drive, to which a gateway connection via EtherCAT ADS is to be

established, in the project tree.

2. Call the menu command Online Set communication path and go online.

3. Select

Gateway Controller -> EtherCAT ADS as bus connection.

4. Enter the access data applicable to the controller in area

.

Enter the user name, password, and the IP address and the AMS Net ID of the EtherCAT

interface of the controller.

5. In area

, specify the EtherCAT address of the field device to which the online connection

is to be established.
Alternatively you can click the Search/Enter button which calls the "Select Device Access

Path" dialog box. By this, the »Engineer« initiates the controller to display the devices

detected on the EtherCAT segment.