Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 105

Advertising
background image

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

105

Troubleshooting

Chapter 15

Figure 123 - Mouse Over to Show Error Message (in Yellow Box)

The type of fault is also shown in the top panel of the Project tab (

Figure 124

).

For a recoverable fault, the Device Details view only indicates “Fault:
Recoverable”. For further details, navigate to the “Logic Editor” view and
mouse over the red marked function block. A user is allowed to change the
operation mode to “Program Mode”

For a nonrecoverable fault, the Device Details view provides the fault type
and status. The device automatically exits “RUN” mode and switches to
“Program mode”. You cannot change the operation mode. Mouse over the
fault status area to get more information.

Figure 124 - Mouse Over Fault in Project Tab

To see a list of the recent faults, click Faults in the Safety Tree.

The recent faults appear in the fault pane.

Click the Export button to export the faults to a comma-separated value (.csv)
file. The default path for Win7 for saving the exported fault log file is the folder
at C:\Users\<user name>\documents\CCW\Fault log.

Advertising