Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 134

134
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Appendix A
Specifications
Table 30 - For SMF1 - E-stop:
It takes 360 ms to enable the outputs when the E-stop is active (closed contacts).
Table 31 - For SMF2 – Safety Mat:
It takes 110 ms to enable the outputs when the Safety Mat is released.
Comment
Value
Feedback
Disabled for SOF
0 ms
Safety Sensors
Reaction time of sensor device -
considered as 0 ms since mechanical
device only
0 ms
SMF
Configured Input Filter time
10x25 ms = 250 ms
250 ms
Reset/Restart
SOF configured for Automatic
0 s
Logic
Internal execution time to process
input signal, routing, and output
processing 2)
100 ms
SOF
No On delay configured for SOF
0 s
Actuator
Assuming a contactor with a
response time of 10ms
10 ms
Total 360 ms
Comment
Value
Feedback
Disabled for SOF
0 ms
Safety Sensors
Reaction time of sensor device -
considered as 0 ms since mechanical
device only
0 ms
SMF
Input Filter Disabled
0 ms
Reset/Restart
SOF configured for Automatic
0 ms
Logic
Internal execution time to process
input signal, routing and output
processing 2)
100 ms
SOF
No On delay configured for SOF
0 s
Actuator
Assuming a contactor with a
response time of 10 ms
10 ms
Total 110 ms