Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Appendix A

Specifications

Table 30 - For SMF1 - E-stop:

It takes 360 ms to enable the outputs when the E-stop is active (closed contacts).

Table 31 - For SMF2 – Safety Mat:

It takes 110 ms to enable the outputs when the Safety Mat is released.

Comment

Value

Feedback

Disabled for SOF

0 ms

Safety Sensors

Reaction time of sensor device -
considered as 0 ms since mechanical
device only

0 ms

SMF

Configured Input Filter time
10x25 ms = 250 ms

250 ms

Reset/Restart

SOF configured for Automatic

0 s

Logic

Internal execution time to process
input signal, routing, and output
processing 2)

100 ms

SOF

No On delay configured for SOF

0 s

Actuator

Assuming a contactor with a
response time of 10ms

10 ms

Total 360 ms

Comment

Value

Feedback

Disabled for SOF

0 ms

Safety Sensors

Reaction time of sensor device -
considered as 0 ms since mechanical
device only

0 ms

SMF

Input Filter Disabled

0 ms

Reset/Restart

SOF configured for Automatic

0 ms

Logic

Internal execution time to process
input signal, routing and output
processing 2)

100 ms

SOF

No On delay configured for SOF

0 s

Actuator

Assuming a contactor with a
response time of 10 ms

10 ms

Total 110 ms