2080-iq4, 2080-ob4, 2080-iq4 2080-ob4 – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

89

Plug-in Modules

Chapter 12

2080-IQ4

The 2080-IQ4 has four sinking inputs. The four COM connections, A3, A4, B3,
and B4 are internally connected. At least one COM connection must be
connected to 24V Com (without it, the inputs do not turn on).

Figure 109 - 2080-IQ4 Schematic Showing Four Standard Input Signals

2080-OB4

The 2080-OB4 has four sourcing outputs. Terminals B3 and B4 are internally
connected; one of these terminals must be connected to +24V DC. Terminals A3
and A4 are internally connected; one of these terminals must be connected to
24V Com.

Figure 110 - 2080-OB4 Schematic Showing Four Standard Output Signals

COM

I-02 I-03

A1 A2

B5

B2

B1

B3 B4

B6

COM COM

I-00 I-01

2080-IQ4

A5

A3 A4

A6

COM NU NU

NU

NU

+24V DC

24V Com

NU

NU

A1 A2

B5

B2

B1

B3 B4

B6

NU

NU

2080-OB4

A5

A3 A4

A6

-24DC

-24DC

O-02 O-03

+24DC

+24DC

O-00 O-01

+24V DC

24V Com

Advertising