Safety Monitoring Functions

Chapter 9

Figure 57 - Wiring Connection for a Reset Signal to Terminal 00

The reset block works with one or more output blocks. When an output block
requires a manual reset, the CCW shows all available reset inputs that can be
used.

Restart

The restart function works with an AND or OR logic block in Logic Level A and
Logic Level B. When all inputs are satisfied, exercising the restart input causes the
restart function go be effective. If the Restart function is already effective, the
Restart input has no affect.

The Restart can only be used with one AND or OR logic block.

Figure 58 - Restart Function Block

The Restart Function requires a leading edge and trailing edge within a specific
time frame. The pulse width must be between 250…3000 ms. If the pulse width is
too short or too long, the Restart function will not be executed.

Figure 59 - Restart Timing

The available input selections for the Restart are:

EI_00…EI_11 (embedded input terminals 00…11)

MP_12…MP_17 (multi-purpose terminals 12…17)

P1_00…P1_03 (plug-in 1 terminals 00…03)

P2_00…P2_03 (plug-in 2 terminals 00…03)

SP_00…SP_15 (Modbus inputs 00…15)

+24V DC

Reset

24V Com

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

+24V DC

24V Com

250ms to

3000 ms