Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 96

Advertising
background image

96

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Chapter 14

Modbus Communication

Figure 113 - (Non-)Readable Pass-through Blocks

000377…000392

Ready-to-start of SOF 00…15

000393…000416

Fault bit 0 of SMF 0…23
00: No error
01: Crossloop
10: Simultaneity fault
11: One channel open after reset

000417…000440

Fault bit 1 of SMF 1…24

000441…000464

Fault bit 2 of SMF 1…24

000465…000488

Fault bit 3 of SMF 1…24

000489…000504

Retrigger Fault SOF 1…16

000505…000512

Cross Fault of Terminals 12…17

000513…000848

Reserved

000849…000860

Fault log

(1) When a Logic Level A block is automatically created as a Pass Through, the block does not

occupy memory and cannot be read over Modbus. This can be viewed in the CCW as a block
with no title. Pass Through blocks in Logic Level B can be read over Modbus.