Configuring the CR30

Chapter 4

15.

File transfer successful or failed.
a. File transfer successful.

Click Yes to change the relay to Run mode. For unverified
configuration, this allows the CR30 to operate for a maximum duration
of 24 hours to perform relevant tests to validate the safety function.
Click No to maintain the relay in Program mode and continue with the
verification process.

b. File transfer failed.

If the transfer file verification failed, the following message occurs.
Click OK and repeat steps 11…15.

Validation and Verification

To complete the safety system requirements, the configuration of the CR30 must
be validated and verified. At the first download, any configuration is in an
unverified state. This means that you have not confirmed that the configuration
and installation meets all specified operational and environmental requirements
of the machine to which CR30 is to be fitted.

Validation

You must perform appropriate testing to validate the configured safety function
of the CR30. Entering Run mode after first download enables operation of a
maximum duration of 24 hours to execute relevant tests of the safety function.
The CR30 displays the execution of an unverified configuration by a flashing
Power LED. After 24 hours, the CR30 stops operation and the power to the
CR30 must be cycled to restore the operation for another 24 hours.

ATTENTION: Before installation, a risk assessment must be performed to
determine whether the specifications of this device are suitable for all
foreseeable operational and environmental characteristics of the machine to
which it is to be fitted. At regular intervals during the life of the machine, check
whether the characteristics foreseen remain valid.