Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

133

Specifications

Appendix A

Reaction Time

The reaction time is the time to enable the safety output function when
activating the safety input devices and performing a valid reset operation. The
overall reaction time of the safety function considers the whole safety chain,
including the safety input device, logic device, and actuator. The reaction time
must be calculated for each safety function.

Table 29

shows the possible chain with all considerable reaction times for a safety

function.

Table 29 - Safety Function Reaction Times

Figure 134 - Example 1:

Description

Where to find:

Value

Feedback

Feedback Input Filter time

From SMF configuration
“advanced settings”

(3)

(3) The maximum input filter time must not be greater than 250 ms.

Safety Sensors

Reaction time of sensor
device

Sensor operating manual

SMF

Configured Input Filter
time

From SMF configuration
“advanced settings”

(3)

Reset/Restart

Reset/Restart Pulse Time +
2 x Filter Time

(1)

(1) If input filter time settings are not disabled, the recommended setting is “0”. Values greater “0” must be considered for the

reaction time.

Reset Pulse: max 3s
Input Filter Time from SMF
configuration

3s + 2 x Input Filter

Logic

Internal execution time to
process input signal,
routing, and output
processing

(2)

(2) The internal execution time is static and independent of the number of function blocks that are configured for the safety function.

From technical
specification

100 ms

SOF

Configured On-Delay time

From SOF configuration

Actuator

Safety switching device
controlling the load

Actuator Operating manual

Total