Chapter 5

Pulse Testing

Then a sequence occurs in which each output is individually tested twice. The
test pulse is 50 μs wide. The test pulses occur every 250 ms and switch to the next
output configured with testing.

Figure 22 - Test Pulse Sequence

Terminal 13

Terminal 12

24V

0V

24V

0V

Terminal 20

Terminal 21

24V

0V

24V

0V

0

250

500ms