56

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Chapter 9

Safety Monitoring Functions

Figure 50 - Example Schematic for 2-Sensor L-Type Muting

For simplicity, the power and ground connections of the light curtain and muting
sensors are not shown. The light curtain and muting sensors must have the same
reference (24V Com) as the CR30 for proper operation.

For proper operation, the muting sensors are on (normally closed) when not
muting, and the light curtain OSSD outputs are also on (the light curtain is
clear).

Figure 51 - Muting Time for 2-Sensor L-Type Muting

+24V DC

Light Curtain

24V Com

MS1

MS2

A

OSSD A

OSSD B

Override

Contactors

for Conveyor Power

Muting Lamp

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

K2

K1

LC

Muting sensor 1

Muting sensor 2

Muting lamp

t > 30ms

t > 30ms

t > 50ms

30ms <= t

t < synchronization

time

30ms <= t

t < synchronization

time

t < muting time

muted