Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

21

Power, Ground, and Wiring

Chapter 3

Grounding the Configurable
Safety Relay

This product is intended to be mounted to a grounded mounting surface such as
a metal panel. See the

Industrial Automation Wiring and Grounding Guidelines,

publication

1770-4.1

, for more information.

Connecting a Power Supply

Power for the relay is provided by an external 24V DC power supply source.

To comply with the CE Low Voltage Directive (LVD), the I/O must be powered
by a DC source compliant with Safety Extra Low Voltage (SELV) or Protected
Extra Low Voltage (PELV).

To comply with UL restrictions, I/O must be powered by DC sources whose
secondary circuits are isolated from the primary circuit by double insulation or
reinforced insulation. The DC power supply must satisfy the requirements for
Class 2.

The following Rockwell Automation power supplies are SELV- and PELV-
compliant, and they meet the isolation and output hold-off time requirements of
the CR30 relay:

2080-PS120-240VAC

1606-XLP30E

1606-XLP50E

1606-XLP50EZ

1606-XLP72E

1606-XLP95E

1606-XLDNET4

1606-XLSDNET4

Figure 5 - Power Supply

WARNING: All devices that are connected to the RS-232 communication port
must be referenced to controller ground, or be floating (not referenced to a
potential other than ground). Failure to follow this procedure can result in
property damage or personal injury.

+DC

24V

COM

0V

Input Terminal Block

Input/Output Terminal Block

09

10

11

12

A2

A1

13

14

15

16

17

18

19

20

21

+24V DC

24V Common

00

01

02

03

04

05

06

07

08