Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

135

Specifications

Appendix A

Figure 135 - Example 2: Same as

Figure 134 on page 133

but with manual monitored reset and

feedback monitoring

Table 32 - For SMF1 - E-stop:

It takes a minimum of 1.36 s, after a valid Reset operation of at least 250 ms to
enable the outputs when the E-stop is active (closed contacts).

Comment

Value

Feedback

Configured Input Filter time
10x25 ms = 250 ms

250 ms

Safety Sensors

Reaction time of sensor device -
considered as 0 ms since mechanical
device only

0 ms

SMF

Configured Input Filter time
10x25 ms = 250 ms

250 ms

Reset/Restart

Min: 2 x Input Filter Time + 250 ms =
500ms + 250 ms = 0.75 s
Max: 2 x Input Filter Time + 3 s = 0.5
+ 3 s = 3.5 s

Min: 0.75 s
Max: 3.5 s

Logic

Internal execution time to process
input signal, routing, and output
processing 2)

100 ms

SOF

No On delay configured for SOF

0 s

Actuator

Assuming a contactor with a
response time of 10 ms

10 ms

Total Min: 1.36 s

Max: 4.11 s