Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Appendix A

Specifications

Table 33 - For SMF2 - Safety Mat:

It takes a minimum of 1055 s, after a valid Reset operation of at least 250 ms to
enable the outputs when the E-stop is active (closed contacts).

Comment

Value

Feedback

Configured Input Filter time
10x25 ms = 250 ms

250 ms

Safety Sensors

Reaction time of sensor device -
considered as 0 ms since mechanical
device only

0 ms

SMF

Input Filter Disabled

0 ms

Reset/Restart

Min: 2 x Input Filter Time + 250 ms =
500ms + 250 ms = 0.75 s
Max: 2 x Input Filter Time + 3 s = 0.5
+ 3 s = 3.5 s

Min: 0.75 s
Max: 3.5 s

Logic

Internal execution time to process
input signal, routing, and output
processing 2)

45 ms

SOF

No On delay configured for SOF

0 s

Actuator

Assuming a contactor with a
response time of 10 ms

10 ms

Total Min: 1.055 s

Max: 3.3 s