Safety Monitoring Functions

Chapter 9

Figure 72 - Wiring Connection for a Type IIIC Two-hand Control with Test Pulses

The timing diagram for the two-hand control is shown in

Figure 73

. The Type

IIIA uses only the N.O. contact of the button. The Type IIIC uses both the N.C.
and the N.O. contacts.

Figure 73 - Two-hand Control Timing Diagram

Description

Description

1

Hand 1 button is pressed.

5

Hand 2 button is pressed.

2

Hand 2 button must be pressed within 500 ms
for the output logic to turn ON.

6

Hand 1 button must be pressed within 500 ms
for the output logic to turn ON.

3

Releasing either hand button causes the logic
output to turn off.

7

Releasing either hand button causes the logic
output to turn off.

4

Both hand buttons must be released to start a
new cycle.

8

Both hand buttons must be released to start a
new cycle.

+24V DC

24V Com

A B

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

Logic Output

Hand 1 N.C.

Hand 1 N.O.

Hand 2 N.C.

Hand 2 N.O.

HI

LO

HI

LO

HI

LO

HI

LO

HI

LO

1

4

3

2

5

6

7

8

must be less than 500ms