Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Chapter 3

Power, Ground, and Wiring

Wire Size

Table 1 - Wiring Requirements

Terminal Assignments

Some terminals are designed to have one specific function. Some terminals can
perform multiple functions; these terminals must be configured in the
application software.

Table 2 - Terminal Assignments

Wire Size

Type

Min

Max

Copper

Stranded

0.326 mm

2

(22 AWG)

1.31 mm

2

(16 AWG)

Rated @ 90 °C (194 °F)
insulation min.

Terminal

Function

00

Safety Input (N.C.)

01

Safety Input (N.C.)

02

Safety Input (N.C.)

03

Safety Input (N.C.)

04

Safety Input (N.C.)

05

Safety Input (N.C.)

06

Safety Input (N.C.)

07

Safety Input (N.C.)

08

Safety Input (N.C.)

09

Safety Input (N.C.)

10

Safety Input (N.C.) or Single Wire Safety Input

11

Safety Input (N.C.) or Single Wire Safety Input

+24V DC

A1 Power Supply (+24V, -15%, +10%)

COM 0V

A2 Power Supply (0V)

12

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

13

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

14

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

15

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

16

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

17

Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.

18

OSSD High Side

19

OSSD High Side

20

OSSD High Side or Single-wire Safety Output

21

OSSD High Side or Single-wire Safety Output