On delay – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 83
Advertising
![background image](/manuals/578132/83/background.png)
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
83
Safety Outputs
Chapter 11
ON Delay
The ON Delay block turns on the output after the specified time delay expires.
shows the ON Delay output block that is connected to an E-stop
block through Logic Level LLB1. The feedback signal is provided by SMF2 and
manual reset by SMF3. The time delay is set to 20. The output will turn on 1000
ms (20x50 ms) after the reset button is released. The output is connected to:
•
Terminals 18 and 19 for dual channel safety switching of the machine
hazards.
•
Terminal 20, which is configured as a Single Wire Safety (SWS) output.
•
Plug-in 1 terminal 00 for status indication.
Figure 102 - ON Delay Configuration
Advertising