General, Environmental, General environmental – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 122

Advertising
background image

122

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Appendix A

Specifications

General

➊ Power has to be supplied by a power supply that complies with IEC / EN 60204 and IEC / EN 61558-1. Such a power supply meets the

electrical safety requirements and maintain the minimum power of 18V DC during 20 ms even in the event of voltage dips.

Environmental

Number of I/O

22

Dimensions

90 x 100 x 80 mm (3.54 x 3.94 x 3.15 in.)

Shipping Weight, approx.

0.423 kg (0.933 lb)

Wire Size

0.2…2.5 mm

2

(24…12 AWG) solid copper wire or

0.2…2.5 mm

2

(24…12 AWG) stranded copper wire

rated @ 90 °C (194 °F) insulation max

Wiring Category

2 – on signal ports
2 – on power ports
Use this Conductor Category information for planning conductor routing. See Industrial
Automation Wiring and Grounding Guidelines
, publication 1770-4.1.

Insulation Stripping Length

7 mm (0.28 in.)

Terminal Screw Torque

0.6 N•m (4.4 lb•in) max
(Using a 2.5 mm (0.10 in.) flat-blade screwdriver)

Input Circuit Type

24V DC source

Output Circuit Type

24V DC source

Power Supply Voltage Range

24V DC +10% -15% ➊

Fuse Specification

6 A

Power Consumption

5.28 W

I/O Rating

Input 24V DC, 4 mA
Output 24V DC, Class 2, 0.5 A per point

Enclosure Type Rating

IP20

Temperature, Operating

-5…+55 °C (23…131 °F)

Relative Humidity

90%

Vibration

10…55 Hz, 0.35mm

Shock

10 g, 16 ms

Pollution Level

2