Dual channel – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 69

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
69
Safety Monitoring Functions
Chapter 9
Figure 75 - Example Schematic for Single Channel N.C. without Test Pulse
Figure 76 - Example Schematic for Single Channel N.C. with Test Pulse
Figure 77 - Example Schematic for Single Channel OSSD
Dual Channel
Dual channel safety monitoring functions require two independent circuit
connections to the CR30. Dual channel inputs are used for medium and high risk
applications.
You can modify the number and types of inputs:
•
2 N.C.
•
2 OSSD
•
1N.C./1 N.O.
The available input selections for the dual-channel OSSD and two N.C.
inputs are:
•
EI_00…EI_11 (embedded input terminals 00…11)
•
MP_12…MP_17 (multi-purpose terminals 12…17)
The available input selections for the N.O. contact are:
•
MP_12…MP_17 (multi-purpose terminals 12…17)
+24V DC
24V Com
05
CR30
02
01
00
03 04
A1
15
20 21
16
06
18
A2
07
19
08
10 11
12 13 14
09
17
A
+24V DC
24V Com
05
CR30
02
01
00
03 04
A1
15
20 21
16
06
18
A2
07
19
08
10 11
12 13 14
09
17
+24V DC
24V Com
Safeguarding
Device
A1
A2
05
CR30
02
01
00
03 04
A1
15
20 21
16
06
18
A2
07
19
08
10 11
12 13 14
09
17