Controller status leds – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 93

Advertising
background image

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

93

LEDs

Chapter 13

In the previous example:

a. Input LED 1 is monitoring a terminal status. In this case, it is

monitoring terminal 01. When the signal to terminal 1 is HI, the LED
is on. When the signal to terminal 1 is LO, the LED is off. If this were a
single channel input, then the LED provides all information that we
need to know about the input.

b. Input LED 2 is monitoring safety monitoring function 1. If the LED is

on, then we know that all inputs are satisfied for whatever function (for
example, dual channel input, muting, or two-hand control) is being
monitored.

c. Output LED 3 is monitoring the status of a Safety Output Function. In

this case, SOF 1 is being monitored. If SOF 1 is driving four outputs
(two safety, one diagnostic, and one Modbus), we expect all four
outputs to be HI when LED 3 is on.

Controller Status LEDs

The CR30 has five module status LEDs that are described in

Table 15

.

Table 15 - Status LEDs

LED

Color

Indicates

POWER

Off

No input power or power error condition

Green

Power on

RUN

Off

Program mode

Green

Run mode

Flashing Green [2 Hz]

Application is running but not verified

FAULT

Off

No fault detected

Red Flashing [2 Hz]

Application fault detected, recoverable

Red

Controller hardware faulted, non-recoverable

LOCK

Off

Not used

COM

Off

No communications

Green

Communications by serial port or USB

Advertising