Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 126
Advertising
![background image](/manuals/578132/126/background.png)
126
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Appendix A
Specifications
Figure 132 - Example
Table 23 - For SMF1 - E-stop:
A demand of the E-stop will force a safe state after 325 ms.
Comment
Value
Safety Sensors
Safety response time of sensor device
- considered as 0 ms since
mechanical device only
0 ms
SMF
An E-stop SMF does not require extra
processing time
0 ms
Input Filter
Advanced Settings: Input Filter: 10 x
25 ms = 250 ms
250 ms
Logic
Internal execution time to process
input signal, routing, and output
processing
45 ms
SOF
Configured Off-Delay time -
immediate OFF
0 ms
Actuator
Assuming a contactor with a
response time of 30 ms
30 ms
Total
325 ms