126

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Appendix A

Specifications

Figure 132 - Example

Table 23 - For SMF1 - E-stop:

A demand of the E-stop will force a safe state after 325 ms.

Comment

Value

Safety Sensors

Safety response time of sensor device
- considered as 0 ms since
mechanical device only

0 ms

SMF

An E-stop SMF does not require extra
processing time

0 ms

Input Filter

Advanced Settings: Input Filter: 10 x
25 ms = 250 ms

250 ms

Logic

Internal execution time to process
input signal, routing, and output
processing

45 ms

SOF

Configured Off-Delay time -
immediate OFF

0 ms

Actuator

Assuming a contactor with a
response time of 30 ms

30 ms

Total

325 ms