Cr30 hardware details, Max number of inputs and outputs – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Chapter 1

Overview

CR30 Hardware Details

Figure 2 - Hardware Details

Max Number of Inputs and Outputs

Many of the inputs and outputs can be configured for different roles. The
following table shows the maximum number of terminals for a specific function.
Assigning a configurable terminal to one role reduces the risks of its use as
another role and reduce the allowed maximum number of terminals for other
functions.

Description

Description

1

Status indicators

10

Verification button

2

Plug-in latch

11

Din Rail mounting latch

3

Plug-in screw hole

12

Input status

4

40-pin high-speed plug-in connector

13

Power status

5

I/O and Power terminal blocks

14

Run status

6

Mounting screw hole/mounting foot

15

Fault status

7

Right-side cover

16

Lock status

8

RS-232 non-isolated serial port

17

Serial communications status

9

Type B connector USB

18

Output status

Function

Max Allowed

Function

Max Allowed

Safety inputs, normally closed

up to 18

Pulse test outputs

up to 6

Safety inputs, normally open

up to 6

OSSD safety outputs

up to 10

Single-wire safety input

up to 2

Non-pulsed (standard) outputs

up to 6

Single-wire safety output

up to 2

11

12

13

Status Indicators

14
15

16
17

18

1

10

2

3

4

5

5

6

6

9

8

7

Advertising