Specifications

Appendix A

Table 24 - For SMF2 - Safety Mat

A demand of the Safety Mat will force a safe state after 100 ms.

Monitoring Time - Occurrence of Recoverable Faults and Failures

Recoverable faults as defined earlier (

Chapter 15

- Troubleshooting) are faults

and failures within the connected periphery of the CR30. The ability to detect
faults depends on the wiring, the type of sensor, and the signal evaluation
function that is applied to the circuit. The monitoring time is the amount of time
to evaluate the fault or failure after detection and to initiate appropriate system
response. Recoverable faults can be recovered by removing the fault and cycling
the appropriate input circuit.

The detection of a recoverable fault does not lead to the loss of the safety
function. When the safety function is demanded during the monitoring time,
after the occurrence of a recoverable fault, the system will respond within the
safety response time according to the response time considerations of this safety
function (See

System Response Time Calculation on page 124

).

Note:

Monitoring measures that are provided by CR30 to the periphery

define the diagnostic coverage of the application and thus the safety rating.
Internal monitoring measures related to a fail-safe design of CR30 are only
related to the safety integrity of the CR30 itself, see “nonrecoverable”
faults.

Examples of recoverable faults include:

Cross loop and shorts to 24V and COM faults

Input discrepancy

Muting: Synchronization times exceed

Muting time exceeded

Muting sequence fault

Two-hand discrepancy fault

Reset/Restart timing fault

Comment

Value

Safety Sensors

Safety response time of sensor device
- considered as 0 ms since
mechanical device only

0 ms

SMF

Safety mat processing time

25 ms

Input Filter

Advanced Settings: Input Filter: 0 ms

0 ms

Logic

Internal execution time to process
input signal, routing, and output
processing

45 ms

SOF

Configured Off-Delay time -
immediate OFF

0 ms

Actuator

Same contactor is controlled by the
safety mat SMF as by the E-stop

30 ms

Total

100 ms