Chapter 9

Safety Monitoring Functions

If a short circuit occurs on terminal 12 to ground, the CR30 turns off its safety
outputs within 3.3 seconds. Remove the fault and cycle the contacts to clear the
fault.

If a short circuit occurs from terminal 12 to terminal 13, the CR30 turns off its
safety outputs within 35 ms. Remove the fault and cycle the contacts to clear the
fault.

Three Channel

The CR30 can accept three channels into one safety monitoring function. All
three inputs must be HI to satisfy the input. If any one of the inputs goes LO, the
output of safety monitoring function goes LO and turns off its associated output
devices. The three N.C. inputs can be operated without input test pulses, with
one input test pulse, with only two input test pulses, or with three input test
pulses.

The available input selections for the three channel inputs are:

EI_00…EI_11 (embedded input terminals 00…11)

MP_12…MP_17 (multi-purpose terminals 12…17)

Pulse testing can be set to 1 Source, 2 Sources, 3 Sources, or Disabled. When 1, 2,
or 3 Sources is selected, the next available test sources are automatically assigned
by the CCW. You can modify the sources afterward.

You can use the default Discrepancy Time and Input Filter or choose to modify
these settings.

The three terminals do not necessarily have to be consecutive.

Figure 84 - Example Schematic for Three N.C. without Test Pulses

Figure 85 - Example Schematic for Three N.C. with One Test Pulse Source

+24V DC

24V Com

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

+24V DC

24V Com

A

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

Advertising