The CR30 uses Modbus RTU communications to transfer status information
and control signals to Micro800® controllers and human-machine interfaces like
the Allen-Bradley PanelView.

The Modbus configuration of the CR30 is fixed to Modbus RTU slave at
address 1.

For more information on PanelView, refer to the following documents:

User Manual: 2711C-UM001_-EN-P

Quick Start Guide: 440C-QS001_-EN-P

Modbus Mapping

The CR30 Modbus addresses are mapped to parameters shown in

Table 16

. The

addresses in the range of 1…512 can be accessed as coils. The fault log can be
accessed by holding register reads; each address contains 16 bits of data.

Table 16 - Modbus Addresses

Modbus Address

Parameter

000001…000016

Modbus serial input data

000025…000028

Input Data for Plug-in 1 Terminals I-00…I-03

000033…000036

Output Data for Plug-in 1 Terminals O-00…O-03

000265

Processor HW fault

000266

Safety Input HW fault

000267

Safety Output HW fault

000268

Power supply fault / Main transistor fault

000269

Communication fault

000270

Configuration fault (wrong revision, invalid configuration)

000271

Time out (Clock monitoring)

000272

Plug-in fault

000273…000294

State of Embedded Terminals 00…21

000297…000300

Input of Plug-in 2 Terminals I-00…I-03

000301…000304

Output of Plug-in 2 Terminals O-00…O-03

000305…000328

State of Safety Monitoring Function (SMF) 0…23

000329…000344

State of Logic Level A Instance (LLA) 0…15

(1)

000345…000360

State of Logic Level B Instance (LLB) 0…15

000361…000376

State of Safety Output Function (SOF) 0…15