Type iiia two-hand control, Type iiic two-hand control – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 66

Advertising
background image

66

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

Chapter 9

Safety Monitoring Functions

Type IIIA Two-hand Control

The Type IIIA uses only one normally open contact for each hand. This
configuration can be set up with or without the use of test pulses. The test pulses
provide short circuit fault detect between channels and between channel and
24V.

Figure 69 - Example Wiring Connection for a Type IIIA Two-hand Control without Test Pulses

Figure 70 - Wiring Connection for a Type IIIA Two-hand Control with the Test Pulses

Type IIIC Two-Hand Control

The Type IIIC uses a normally open and a normally closed contact for each hand.

Figure 71 - Example Wiring Connection for a Type IIIC Two-hand Control without Test Pulses

When test pulses are used, the CR30 will detect a short from Channel 1 to
Channel 2 after 3.7 seconds and turn the output OFF. To clear the fault, release
both buttons.