Chapter 4

Configuring the CR30

Verification

After validation, you can assign a unique verification ID to the current
configuration in Connected Components workbench. Any change to a verified
configuration invalidates the verification ID and requires a new validation and
verification process.

To complete the validation and verification, you finally have to acknowledge that
the safety configuration and installation meets the operational and
environmental specification of the machine. Relevant documentation:

Details of the authorized and responsible personnel

Revision of the firmware of the CR30

Version of the Connected Components workbench

Identification of the configured safety function and project

16.

The CCW must be connected to the CR30 during verification.

17.

The CR30 must be in Program mode.

18.

Click the Verify button (the Safety Verification window appears).

19.

Answer all questions and check each box, if completed.

20.

Click Generate.

IMPORTANT

The verification process must be documented in the safety system
technical file.

Use the

Configuration Reference Document on page 139

or the verification

report feature in CCW release 7 or higher.

ATTENTION: The verification process should be documented in the safety
system technical file.