Safety Monitoring Functions

Chapter 9

Figure 80 - Example Schematic for Two OSSD

Dual Channel N.C./N.O.

The N.C./N.O. configuration applies the diversity concepts, where one contact
is open and the other contact is closed. The contact, while in an open state,
cannot be welded closed. The CR30 turns off its safety outputs when either
channel changes state. Both channels must change state for proper performance.

Figure 81 - Example Schematic for N.C./N.O. without Test Pulse

Figure 82 - Example Schematic for N.C./N.O. with One Test Pulse

Figure 83 - Example Schematic for N.C./N.O. with Two Test Pulses

If a short circuit occurs on terminal 12 to 24V, the CR30 turns off its safety
outputs within 35 ms. Remove the fault and cycle the contacts to clear the fault.

+24V DC

24V Com

Safeguarding

Device

A1
A2

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

+24V DC

24V Com

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

+24V DC

24V Com

A

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

A B

+24V DC

24V Com

05

CR30

02

01

00

03 04

A1

15

20 21

16

06

18

A2

07

19

08

10 11

12 13 14

09

17

Advertising