Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

91

Options

Chapter 6

Programming Parameters

The following table provides the option-specific parameters that are provided
with each control option. These parameters are in addition to those already
discussed in the Basic Setup and Metering groups. Diagrams supporting the
options described below are shown later in this chapter.

Option

Parameter

Range

Pump Control

Pump Control

SMC Option
This parameter identifies the type of
control present and is not user
programmable.

Pump Control

Pump Stop Time
Allows the user to set the time period
for the pump stopping function.

0 to120 s

Starting Mode
Allows the user to program the SMC
Flex controller for the type of starting
that best fits the application.

Pump Start, Soft Start, Current Limit
Start, Full Voltage

Braking Control

(1)

(1) Braking Control is not offered for standard use in MV applications. Please consult factory for further assistance.

SMB Smart Motor Braking

SMC Option
This parameter identifies the type of
control present and is not user
programmable.

Braking Control

Braking Current

(2)

Allows the user to program the
intensity of the braking current
applied to the motor.

(2) All braking/stopping current settings in the range of 1…100% will provide 100% braking current to the motor.

0…400% of full load current