Voltage sensing board replacement – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 130

Advertising
background image

120

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 9

Troubleshooting

Voltage Sensing Board
Replacement

1.

Ensure there is no power to the equipment.

2.

Mark the position of the ribbon cable and wires.

3.

Remove the screws and lift the ring lugs from the terminals to remove the
wires.

4.

Release the locking mechanism located on each side of the ribbon cable
connector and pull the ribbon cable straight out to prevent bending the
pins.

5.

Remove the 4 nuts that secure the assembly to the side panel.

6.

Replace with the new assembly securing with all 4 nuts and washers. (See

Figure 48

.)

7.

Replace ring lugs on terminals. Plug in ribbon cable making sure that it is
positioned properly and fitting is secure (locking mechanism is engaged).

8.

For personnel and equipment safety, ensure both grounding connections
are reconnected to the sensing board.

Figure 48 - Sensing Board with mounting hardware placement

SHOCK HAZARD: To prevent electrical shock, ensure the main power
has been disconnected before working on the sensing board. Verify that
all circuits are voltage free using a hot stick or appropriate high voltage-
measuring device. Failure to do so may result in injury or death.

Mounting Hardware

Mounting Hardware

Mounting Hardware

Mounting Hardware