Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

161

Parameter Information

Appendix B

Group

Parameter Description

Parameter
Number

Units

Min / Max

Default
Settings

User
Settings

Ground Fault

Gnd Flt Enable

72

Disable
Enable

Disable

Gnd Flt Level

73

A

1.0…5.0

2.5

Gnd Flt Delay

74

SEC

0.1…250.0

0.5

Gnd Flt Inh Time

75

SEC

2.25

10

Gnd Flt A Enable

76

Disable
Enable

Disable

Gnd Flt A Lvl

77

A

1.0…5.0

2.0

Gnd Flt A Dly

78

SEC

0…250

10

PTC

PTC Enable

79

Disable
Enable

Disable

Phase Reversal

Phase Reversal

80

Disable
Enable

Disable

Restart

Starts Per Hour

81

0…99

2

Restart Attempts

82

0…5

2

Restart Delay

83

SEC

0…60

0

Comm Masks

Logic Mask

87

8-bit binary

Data Links

Data In A1

88

Data In A2

89

Data In B1

90

Data In B2

91

Data In C1

92

Data In C2

93

Data In D1

94

Data In D2

95

Data Out A1

96

Data Out A2

97

Data Out B1

98

Data Out B2

99

Data Out C1

100

Data Out C2

101

Data Out D1

102

Data Out D2

103

Motor Data

Motor ID

104

0…65535

0

CT Ratio

(1)

105

1…1500

MV Ratio

(2)

106

1…10000

(1) Program the module for primary current rating (eg. 150:5 CT, program 150).
(2) Refer to

Chapter 3, Commissioning Procedure

, to determine the appropriate setting.