Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 36

Advertising
background image

26

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 1

Product Overview

If the motor has started, the unit is in the bypass mode, and a trip occurs within
the SMC Flex module or from an external protection relay; “Aux #4” will open
the line contactor immediately, and “Aux #1” will remain closed for 10 seconds to
protect the power electronics from any voltage transients due to opening the
motor circuits. A trip due to an overload or fault condition will result in a “coast”
stop.

Bulletin 1562E • DPI Control – Controlled Start only

The control scheme shown in

Figure 22

allows the MV SMC Flex to be

controlled using DPI (Drive Programming Interface). (

Table 16 on page 109

for

Logic Command Word bits assignment for DPI control.) This special usage of
DPI includes provisions for a “Local” mode of control as well.

With the Local-Off-Remote selector switch in the “Remote” position, terminal
18 of the SMC Flex module is energized, allowing a start command to be
executed via DPI. When a “Start” is executed, the “Aux #4” contact closes,
energizing both “M-IV” and “MCX”. The line contactor closes and the unit
initiates a start sequence.

When the motor approaches rated speed, the SMC Flex module closes “Aux #1”,
energizing “B-IV”, which closes the bypass contactor.

To run in “Local” mode, the “CR” contact is used to initiate a start sequence
(similar to

Figure 20

).

A stop command can be generated via DPI or by opening “CR”, depending on the
control mode.

Bulletin 1562E • DPI Control – With Controlled Stop

The control scheme shown in

Figure 23

allows the MV SMC Flex to be

controlled using DPI (Drive Programming Interface). (

Table 16 on page 109

for

Logic Command Word bits assignment for DPI control). This special usage of
DPI includes provisions for a “Local” mode of control as well.

With the Local-Off-Remote selector switch in the “Remote” position, terminal
18 of the SMC Flex module is energized, allowing start and stop maneuvers to be
executed via DPI. When a “Start” is executed, the “Aux #4” contact closes,
energizing both “M-IV” and “MCX”. The line contactor closes and the unit
initiates a start sequence.

When the motor approaches rated speed, the SMC Flex module closes “Aux #1”,
energizing “B-IV”, which closes the bypass contactor. When a “Stop” is executed,
the unit opens “Aux #1”. The bypass contactor opens and the unit initiates a
controlled stop sequence, followed by opening of “Aux #4”, which opens the line
contactor.

Advertising