1560E and 1562E Relay Control

Functional Description

The following functional descriptions and associated control circuits are for units
using electromechanical (relay) control.

Bulletin 1562E • Basic Control – Controlled Start only

When wired as shown in

Figure 71

, the controller operates as follows:

Pressing the “Start” button initiates the start sequence. Relay “CR” closes and
applies control power to terminal 17 of the SMC Flex module. The auxiliary
contact #2 (set for “normal”) closes, picking up “MC”, which completes the hold-
in circuit on the start button, and closes the main contactor.

The SMC Flex module examines the line voltage, looks for fault conditions,
checks phase rotation, calculates zero crossing information, and begins gating the
SCRs to start the motor.

When the motor approaches rated speed, the SMC Flex module closes the
“AUX1” (Ext. Bypass) auxiliary contacts, closing relay “BC”, which closes the
bypass contactor. The motor then runs at full line voltage.

When the “Stop” button is pressed, the “CR” relay opens terminal 17 on the
SMC Flex module. The “AUX4” (Normal) contact opens, dropping out the main
contactor, allowing the motor to stop. The “AUX1” contact is held closed for a
short time by the control module. This holds the bypass contactor closed for
about 10 seconds to protect the power electronics from any voltage transients due
to opening the motor circuits.

Bulletin 1562E • Basic Control – With Controlled Stop

When wired as shown in

Figure 72

, the controller operates in much the same

manner as in

Figure 71

.

Terminal 16 on the SMC Flex module now controls the start and stop
maneuvers. Terminal 16 must remain energized for the module to run. When the
“Stop” button is pressed, and “CR” opens, the SMC Flex module will initiate the
option stop. An uncontrolled, or coast stop, is achieved by opening the
connection to terminal 17. This contact should remain open to ensure all hold-in
contacts clear, to prevent a re-start.