Status indication, Refer to – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 28

Advertising
background image

18

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 1

Product Overview

Status Indication

All auxiliary contacts can be programmed as NO or NC for the following states
except External Bypass, which can only be programmed as NO.

Normal/Normal NC:

The contact state changes when the unit receives a

Start/Stop signal

Up-to-Speed/Up-to-Speed NC:

The contact state changes when the motor

approaches rated speed

Alarm/Alarm NC:

The contact state changes when an Alarm condition is

detected

Fault/Fault NC:

The contact state changes when a Fault condition is detected

Network Control/Network Control NC:

The contact state is controlled over

the network. (Refer to

Table 16 on page 109

, which describes logic command

word to control auxiliary outputs)

External Bypass:

This contact controls the Bypass contactor for MV

applications.

Figure 16 - Control Terminals

Note:

The Aux #1 contact is always programmed for External Bypass (NO) to
control the bypass contactor in MV applications.

The Aux #2 contact is typically programmed for fault indication in MV
applications (it can be configured for NO/NC).

The Aux #3 contact is typically programmed for alarm indication in MV
applications (it can be configured for NO/NC).

The Aux #4 contact is always configured as Normal (NO) to control the
line contactor for MV applications.

TIP

The tag name without a suffix indicates a NO state (e.g. Normal). On the other
hand, a tag name followed by NC indicates a normally closed state (e.g. Normal
NC).

11

12

13

14

15

16

17

18

19

20

21

23

24

25

26

27

28

29

30

31

32

33

34

22

a

SMC Flex Controller Terminals

Opt

Input

#2

Opt

Input

#1

Start

Input

Stop

Input

(External

Bypass)

Aux #1

PTC

Input

TACH

Input

Ground

Fault

(Fault

Contact)

Aux 2

Aux 3

Aux 4

(Alarm

Contact)

(Normal)