Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

63

Commissioning Procedure

Chapter 3

Figure 37 - Connection and Test Information for Interface Board

+5 +15

C

C

C

C

C

C

B

B

B

B

B

B

A

A

A

A

A

A

ROCKWELL

AUTOMATION

SW2: When ON (up) provides
test pulses to gate driver circuits.
NOTE: Must be OFF (down) for
normal operation.

LED (Red): ON when
test pulses on

SMC Flex control module

Ribbon connectors to connect
to SMC Flex control module
(underneath control module)

Current
feedback
test points

Ribbon connector
to Voltage
Sensing Board

TB5:
Current
transformer
connections

LED (Green):

ON when

power is

present

LED (Green):

ON when current

loop power

supply is present

Module common:
Do not connect to

this terminal.

Voltage

feedback

test points

Current loop
power supply
sensor input

LED (Yellow): ON
when Phase C
gate signal active

TP18, 19, 20:
Power supply test
points.

LED (Green): ON when signal present
at temperature feedback fibre optic
receivers

TP15: Common for
Gate/Pulse TPs

TP13: Phase C
gate signal

TP11: Phase B
gate signal

LED (Yellow): ON
when Phase B
gate signal active

TP11: Phase B
gate signal

TP8: Common for
Gate/Pulse TPs

TP4: Phase A
gate signal

LED (Yellow): ON
when Phase A
gate signal active

Phase A

Fibre Optic

Transmitters send

gate signals to

driver boards

Phase B

Fibre Optic

Transmitters

Phase C

Fibre Optic

Transmitters

Temperature

Feedback

Fibre Optic

Receivers

Temp A

Temp B

Temp C

L N G

Control Power

110-240 VAC

L N

Power out to

SMC Flex

Serial
Number

Replacement
Part Number

SW3: Used to
detect temperature
feedback channels

TEMP
DEFEAT

Notes: 1. ICOM is the common connection for Gate and Pulse test points.

2. VCOM is the common connection for Current and Voltage feedback test points. Do not connect J2 (VCOM) to earth

ground; do not connect ICOM and VCOM together, either directly or through test probes, meter or scope common.

ICOM

GATE

PULSE

GATE

PULSE

GATE

PULSE

ICOM

VCOM

TB21

I-A

I-B

I-C

LINE A

LOAD A

LINE B

LOAD B

LINE C

LOAD C

VCOM

TB6

J2

TB5

A-

A+

B-

C-

C+

B+

VCOM