Example settings, Undervoltage, Overvoltage(1) – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 95: Underload(2), Undervoltage overvoltage, Jam underload, Overvoltag e, Underload

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

85

Programming

Chapter 4

Example Settings

Undervoltage

(1)

With Line Voltage programmed for 4160V and the Undervoltage level
programmed for 80%, the trip value is 3328V.

Overvoltage

(1)

With Line Voltage programmed for 3300V and the Overvoltage level
programmed for 115%, the trip value is 3795V.

Jam

(2)(3)

With Motor FLC programmed for 150 Amps and the Jam level programmed for
400%, the trip value is 600 Amps.

Underload

(2)

With Motor FLC programmed for 90 Amps and the Underload level
programmed for 60%, the trip value is 54 Amps.

(1) The average value of the three phase-to-phase voltages is utilized.
(2) The largest value of the three phase currents is utilized.
(3) The SMC Flex will self-protect.