128

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 9

Troubleshooting

Figure 51 - Power Module Assembly (one phase) • 1000/1300/1500/2400V, 180/360A

Figure 52 - Heatsink Clamp

Heatsink 1

Heatsink 3

Heatsink 2

SCR 2

SCR 1

(Do not loosen)

Gap

Center Nut

Locking Nut

(Do not adjust)

Indicating Washer

(Do not loosen)

To remove clamp pressure, loosen lower
center nut so that the gap between the
clamp surface and the heatsink is
approximately 6 mm (0.25 in.).

Advertising