B - parameter information, Parameter list, Appendix b – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 169: Parameter information, T #2. (refer to, Refer to, Appendix

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

159

Appendix

B

Parameter Information

Parameter List

Table 32 - Parameter List

Group

Parameter Description

Parameter

Number

Units

Min / Max

Default

Settings

User

Settings

Metering

Volts Phase A-B

1

V

Volts Phase B-C

2

V

Volts Phase C-A

3

V

Current Phase A

4

A

Current Phase B

5

A

Current Phase C

6

A

Watt Meter

7

KW/MW

Kilowatt Hours

8

KWH/MWH

Elapsed Time

9

Hours

Meter Reset

10

NO
ETM Reset
KWH Reset

NO

Power Factor

11

0.00…0.99

Mtr Therm Usage

12

%

0…100

Motor Speed

13

%

0…100

Basic Set Up

SMC Option

14

Standard Brake
Pump Control

Motor Connection

15

Line/Delta

Line

(2)

(2) Do not set to “Delta”.

Line Voltage

16

V

0…10000

480

Starting Mode

17

Full Voltage
Current Limit
Soft Start
Linear Speed
Pump Start

Soft Start

Ramp Time

18

SEC

0…30

10

Initial Torque

19

% LRT

0…90

70

Cur Limit Level

20

% FLC

50…600

350

Kickstart Time

22

SEC

0.0…2.0

0.0

Kickstart Level

23

% LRT

0…90

0

Option 2 Input

(1)

(1) Pump modules do not display this parameter. Default setting for MV applications is typically ‘Emergency Run’.

24

Disable
Preset SS
Dual Ramp
Fault
Fault NC
Network
Clear Fault
Emergency Run

Disable

Dual Ramp

Starting Mode 2

25

Full Voltage
Current Limit
Soft Start
Linear Speed

Soft Start

Ramp Time 2

26

SEC

0…30

10

Initial Torque 2

27

% LRT

0…90

70

Cur Limit Level 2

28

% FLC

50…600

350

Kickstart Time 2

30

SEC

0.0…2.0

0.0

Kickstart Level 2

31

% LRT

0…90

0