188

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix E

ArcShield Plenum Installation Instructions

Figure 86 - ArcShield Line-up

Plenum exhaust can be on the left or right hand end of the line-up. Pictures and
figures in this procedure are shown for a right hand exhaust exit direction. Also
shown is an optional vertical (top) direction exhaust extension (see

Figure 100

).

STEP 1 – Mounting a Single
Plenum

Before mounting a single Plenum over an MV enclosure, the front duct section
must first be removed. This is shown in

Figure 87

.

Figure 87 - Removing Front Duct Section

Sealed end

36" Exhaust extension

Exhaust end

IMPORTANT

Plenum components not directly mounted to the tops of the MV enclosures,
must have additional mounting support. This includes the Extension
components and 90° Elbow Sections (refer to

STEP 7 – Additional Mounting

Support on page 194

).

Front Duct Section
Components