Control wiring – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 103

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

93

Options

Chapter 6

Control Wiring

Refer to

Chapter 1, Product Overview

for typical control wiring examples used

with various control schemes.

TIP

Options that control the stopping of the motor (Soft Stop, Pump Stop, Linear
Speed, Braking) require the self-powered gate drivers to be pre-charged by the
current loop power supply. If this supply is not present, an alarm symbol will
appear at the upper right corner of the control module display, and the options
will be inhibited. When the motor is stopped, it will coast. If the supply is
restored, the alarm symbol will be cleared and the module will perform the
programmed sequence.

Advertising