Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 166

Advertising
background image

156

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix A

Specifications

Table 30 - Power Fuses and Losses

Description

Specifications

Power Fuses and Fuse Holders

This section details the power fuse and fuse holder technical information that each medium voltage product conforms to.
It includes information on R-rated fuses, as well as mounting dimensions.

Fuse Types

R Rated: 2R to 24R

2R to 24R
19R, 38R
Interrupting Ratings : 2.4 kV to 7.2 kV

A480R – 5.0/2.4 kV
A072 – 7.2 kV
A051B – 5.0/2.4 kV
50 kA RMS SYM (80 kA RMS ASYM)

Mounting (Center) Dimensions

Clip-On

304.8 mm (12.0 in)

Bolt-On

454.2 mm (17.88 in)

Maximum Heat Dissipation (kW) (Convection)

Controller Rating

Start or Stop Cycle

(@ 450% Starting Duty)

Continuous

180 A

360 A

600 A

2500 V

13.5

19.2

45.3

.250

5000 V

27.0

38.5

90.5

.250

7200 V

40.5

57.7

136.0

.250

Power Losses

Power Cell Losses

Current (A)

Fuse Size

Losses (kW)
± 10%

90

6R

.125

180

12R

.350

240

18R

.510

360

24R

1.000

600

57X

1.500

Power Bus Losses

Bus Rating (A)

Fully Loaded Bus
Losses per 915 mm (36 in.) Section
(Watts) ±%

1200

150

2000

200

3000

200

Control Power Transformer Losses

The losses from a 500 VA control power transformer fully loaded are approximately 50 W per controller.

Low Voltage Panel Losses

The losses from the standard control circuit are approximately 25 W per controller.