Unbalance, Stall protection and jam detection, Unbalance stall protection and jam detection – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

11

Product Overview

Chapter 1

Unbalance

(6)

The MV SMC Flex is able to detect an unbalance in line voltages. Motor
operation can be halted if the unbalance is greater than the desired range.

The MV SMC Flex controller provides an adjustable unbalance setting from 0 to
25% of the line voltages. Trip delay time can be adjusted from 0 to 99 seconds.

An alarm (pre-fault) indication level can be programmed to indicate the unit is
getting close to faulting. The alarm modification information is displayed
through the LCD, HIM, Communication (if applicable) and alarm contact
closing.

Stall Protection and Jam Detection

The MV SMC Flex controller provides both stall protection and jam detection
for enhanced motor and system protection.

Stall protection is user-adjustable from 0.0 to 10.0 seconds (enabled only
after the programmed start time expires).

An alarm (pre-fault) indication level can be programmed to indicate the
unit is getting close to faulting. The alarm modification information is
displayed through the LCD, HIM, Communication (if applicable) and
alarm contact closing.

Jam detection allows the user to determine the jam level (up to 1000% of
the motor’s full-load current rating) and the delay time (up to 99.0
seconds) for application flexibility.

Figure 11 - Stall Protection

(6) Undervoltage, overvoltage, and voltage unbalance protection are disabled during braking operation.

Percent

Full Load

Current

600%

Programmed Start Time

Stall

Time (seconds)

Advertising