Motor protection – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 94

Advertising
background image

84

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Chapter 4

Programming

Motor Protection

While the Basic Setup group allows the user to get started with a minimum
number of parameters to modify, the Motor Protection group allows full access
to the SMC Flex controller’s powerful parameter set. Following is a listing of the
additional setup parameters provided.

TIP

The majority of parameters have a Fault and an Alarm setting.

Parameter

Option

Overload
Allows the user to select the operation of the overload.

Trip Class, Service Factor, Motor FLC, Overload Reset,
Overload Alarm Level

Underload

(1)

(2)

Determines the trip level as a percentage of the motor’s
FLA, and the delay period.

(1) The delay time must be set to a value greater than zero when Undervoltage, Overvoltage and Unbalance are enabled.
(2) For Jam and Underload detection to function, the Motor FLC must be programmed in the Motor Protection group. See

Motor

Information on page 86

.

Underload Fault Level,
Underload Fault Delay,
Underload Alarm Level,
Underload Alarm Delay

Undervoltage

(1)

Determines the trip level as a percentage of line voltage
and delay period.

Undervoltage Fault Level,
Undervoltage Fault Delay,
Undervoltage Alarm Level,
Undervoltage Alarm Delay

Overvoltage

(1)

Determines the trip level as a percentage of line voltage
and delay period.

Overvoltage Fault Level,
Overvoltage Fault Delay,
Overvoltage Alarm Level,
Overvoltage Alarm Delay

Unbalance

(1)

Allows the user to set the current unbalance trip level and
delay period.

Unbalance Fault Level,
Unbalance Fault Delay,
Unbalance Alarm Level,
Unbalance Alarm Delay

Jam

(1)

(2)

Determines the trip level as a percentage of motor full
load current and delay period.

Jam Fault Level,
Jam Fault Delay,
Jam Alarm Level,
Jam Alarm Delay

Stall
Allows the user to set the stall delay time.

Stall Delay

Ground Fault

(3)

Allows the user to enable the ground fault level in amps,
delay time and inhibit time. A separate core balance
current transformer is required.

(3) See details in

Ground Fault on page 12

.

Ground Fault Enable,
Ground Fault Level,
Ground Fault Delay,
Ground Fault Inhibit Time,
Ground Fault Alarm Enable,
Ground Fault Alarm Level,
Ground Fault Alarm Delay

PTC

(4)

Allows the user to connect a PTC to the SMC and enable a
fault when it becomes active.

(4) See details in

Thermistor/PTC Protection on page 13

.

PTC Enable

Phase Reversal
Determines the proper orientation of line connections to
the SMC. If Enabled and phases are out of sequence, a
fault will be indicated.

Phase Reversal

Restarts
Allows the user to determine the maximum number of
restarts per hour the unit can experience, and delay time
between consecutive starts.

Restarts Per Hour,
Restart Attempts,
Restart Delay

Advertising