Figure 81, Figure 82 – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 192

Advertising
background image

182

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

Appendix D

ArcShield Unit Information

Figure 81 - Plenum Exit Left with Extension(s) to Internal Controlled Access Area (Top View)

Figure 82 - Plenum Exit Left with Extensions to Internal Controlled Access Area (Front View)

Minimum H = 3.5 m [138 inches]
Minimum L = 1.2 m [47 inches]
Minimum Volume of space required for safe pressure relief:

X *Y* H = 11 m



[390 cubic feet]

Personnel Access Barriers

X

L

Y

Personnel Access
Barriers

L

H

Advertising