Figure 39 – Rockwell Automation MV SMC Flex Motor Controller (for Series K or later) User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

65

Commissioning Procedure

Chapter 3

6.

With the gate pulses on, check the voltage again on each gate driver board
as described in Step 4 above. The voltage should be 4 - 5V DC.

7.

Locate the Portable Test Power Supply that was included with the
equipment, and verify that the rating corresponds to the available power
system (i.e. 110/120 VAC or 220/240 VAC). Plug the unit into the power
source, and plug the green connector into J1 on each of the gate driver
boards (see

Figure 39

.

Figure 39 - Test Power Application on Gate Driver Board

8.

The yellow LED on the upper right-hand side of the energized gate driver
circuit should be lit (it may appear dim, depending on ambient light
conditions). While the gate pulses are still on, check the voltage on each
gate driver board as described in step 4 above. The voltage should be
10-12V DC. If the voltage is less than 5V, then you have a bad gate drive
board. Do not leave the Portable Test Power Supply connected to a bad
gate driver board. The power supply adapter will burn up if the gate driver
board is shorted.

9.

A more detailed check is performed by verifying the actual gate pulses by
connecting an oscilloscope between TP1 and TP3 (-) (see

Figure 39

). To

check gate pulses, the pulse generator must be enabled (i.e. SW2 toggled
up) and the Portable Test Power Supply should be connected to J1. The
pulse should appear as shown in

Figure 40

and

Figure 41

.

Temperature signal
fiber-optic transmitter

Gate signal

fiber-optic receiver

Plug-in test

power supply

Current loop CT

Snubber

terminal

Cathode

terminal

Common

test point

+20V test point

+5V test point

Yellow LED

Thermistor
connector

Gate signal
test point

Overvoltage
sense terminal

J3

J4

J1

TP3

TP4

TP2

TP1

J2

RX2

RX1

J6

Advertising