SMC Flex™ Control Module

The MV SMC Flex controller offers a full range of starting and stopping modes
as standard:

Soft Start with Selectable Kickstart

Soft Stop

Current Limit Start with Selectable Kickstart

Linear Acceleration with Selectable Kickstart

Linear Deceleration

Dual Ramp Start

Preset Slow Speed

(1)

Full Voltage Start

Other features that offer further user benefit include:

Extensive protection features

Metering

Communication capability

I/O

Innovative control option provides enhanced performance:

Pump Control (Start and Stop Control modes)

These modes, features and options are further described in this chapter.

Starting Modes

Soft Start

This mode has the most general application. The motor is given an initial torque
setting, which is user-adjustable from 0 to 90% of locked-rotor torque. From the
initial torque level, the output voltage to the motor is steplessly increased during
the acceleration ramp time. The acceleration ramp time is user-adjustable from 0
to 30 seconds. Once the MV SMC Flex controller senses that the motor has
reached the up-to-speed condition during the voltage ramp operation, the output
voltage automatically switches to full voltage, and the bypass contactor is closed.

Figure 1 - Soft Start

(1) This option utilizes gating patterns which result in motor and line currents that produce noise and vibration in the motor and/or

distribution transformer. This must be considered before applying this option.

Percent
Voltage

100%

Initial

Torque

Start

Time (seconds)

Run