Chapter 1

Product Overview

Protection and Diagnostics

The MV SMC Flex controller is capable of providing the following protective
and diagnostic features:

Overload

The MV SMC Flex controller meets applicable requirements as a motor overload
protection device. Thermal memory provides added protection and is
maintained even when control power is removed. The built-in overload
algorithm controls the value stored in Parameter 12, Motor Thermal Usage
(Refer to

Chapter 4, Programming

). An Overload Fault will occur when this

value reaches 100%. The parameters below provide application flexibility and
easy setup.

Notes:

1.

If the MV SMC Flex is used to control a multi-speed motor, or more than
one motor, the Overload Class parameter must be programmed to “OFF”
and separate overload relays must be supplied for each speed/motor.

2.

Automatic reset of an overload fault requires the start input to be cycled in
a 2-wire control scheme.

3.

The trip rating is 117% of the programmed FLC.

Figure 9

and

Figure 10

provide the overload trip curves for the available trip

classes.

Parameter

Range

Overload Class

Disable, 10, 15, 20, 30

Overload Reset

Manual – Auto

Motor FLC

10 – 2200 amps

Service Factor

0.01 – 1.99

IMPORTANT

During slow speed operations, current waveforms exhibit non-sinusoidal
characteristics. These non-sinusoidal characteristics inhibit the controller's
current-measurement capability. To compensate for additional motor heating
that may result, the controller uses motor thermal modeling, which increments
motor thermal usage. This compensation takes place when the Preset Slow
Speed option is used.