Chapter 9

Troubleshooting

Underload

23

• Broken motor shaft
• Broken belts, tool bits, etc.
• Pump cavitation

• Repair or replace motor
• Check machine
• Check pump system

Jam

24

• Motor current has exceeded the user

programmed jam level

• Correct source of jam
• Check programmed time value

Stall

25

• Motor has not reached full speed by the end of

the programmed ramp time

• Correct source of stall

Phase Reversal

26

• Incoming supply voltage is not in the expected

ABC sequence

• Check power wiring
• Disable protection if not needed

Comm Loss

27, 28, 29

• Communication disconnection at the serial port

• Check for a communication cable disconnection

to the SMC Flex controller

Network

30, 31, 32

• DPI network loss

• Reconnect for each DPI connected device

Ground Fault

33

• Ground fault current level has exceeded

programmed values

• Check power system and motor; correct if

necessary

• Check programmed ground fault levels to

match application requirements

Excess Starts/Hr.

34

• Number of starts in a one-hour period has

exceeded the value programmed

• Wait an appropriate amount of time to restart
• Consult factory if more than 2 starts per hour

are required

Power Loss

(1)

(with phase indication)

35, 36, 37

• Missing supply phase (as indicated)
• Loss of feedback

• Check for open line (i.e., blown line fuse)
• Check CT connections, replace Interface board

HAL_ID

38

• Faulty interface

• Check ribbon cable connections between

interface board and control module

• Check current loop system
• Replace interface board

NVS Error

39

• Data entry error

• Check user data and perform a User Store

function

• Replace control module

Line Loss

41, 42, 43

• Line Distortion
• High impedance connection

• Check supply voltage for capability to start/stop

motor

• Verify system grounding (refer to

Resistance

Checks on page 68 of Chapter 3

)

• Check for loose connections on line side or

motor side power wires

V24 Loss

45

• Internal power supply problem

• Cycle control power to reset the control module
• If Fault persists, replace control module

V Control Loss

46

• Internal sense circuit problem

• Cycle control power to reset the control module
• If Fault persists, replace control module

Option Input 1

48

• External Fault

• Check programming of Parameter 132
• Check status of device connected to Input 1

Option Input 2

49

• External Fault

• Check programming of Parameter 24
• Check status of device connected to Input 2

System Faults

128 to 209

• Control module internal fault

• Cycle control power to reset the control module
• If fault persists, replace control module

(1) Prestart fault indication

Display

Fault Code

Possible Causes

Possible Solutions