Rockwell Automation Publication 1560E-UM051F-EN-P - June 2013

163

Parameter Information

Appendix B

Group

Parameter Description

Parameter

Number

Units

Min / Max

Default

Settings

User

Settings

Linear List

Fault 1

124

0…255

Fault 2

125

0…255

Fault 3

126

0…255

Fault 4

127

0…255

Fault 5

128

0…255

Basic Set Up

Option 1 Input

132

Disable
Stop Option
Fault
Fault NC
Network

Stop
Option

Stop Input

133

Coast
Stop Option

Coast

Tuning and Special Parameters

(Visible with 6.001 and later firmware.)

(Visible and writable only with Password

1196 on 5.00n and earlier firmware.)

Pump Pedestal

34

%

0…50

0

(2)

Braking Time

36

Sec

0…999

0

(3)

Load Type

37

Standard
High Inertia
High Friction
Ramp 89

Standard

(2)

High Eff. Brake

38

%

0…99

0

(3)

OL Shunt Time

48

Sec

0…999

0

OL Trip Enable

49

Disable
Enable

Enable

Line Fault

84

Disable
Disable F1
Disable F41
Enable

Enable

Emergency Run

85

Disable
Enable

Disable

Current Loss

86

Disable
Enable

Enable

Timed Start

112

Disable
Enable

Disable

See Param.

#114

I Shutoff Level

113

%

0…37

0

Do not

change

UTS Level

114

%

0…100

75

V Shutoff Level

117

%

0…100

25

OL Reset Level

118

%

0…99

75

Ambient Temp.

119

0…60

50

Do not

change

Notch Position

120

%

40.0…100.0

87.5

Do not

change

Notch Maximum

121

50…70

70

Do not

change

Start Delay

122

Sec

0…30

0

Bypass Delay

123

Sec

0…15

0

Start Time E

129

Sec

0…999

0

Start Time E2

130

Sec

0…999

0

Stop Time E

131

Sec

0…999

0

Elapsed Time 2

134

Hours

0…3000

(1)

(1) Read-only parameter
(2) Pump modules only
(3) Brake modules only